      Scenario 9



Related PDF's

Corporate Capabilities Brochure

Assuring the Availability of Network Closets and Computer Rooms

Overview


Room size (square feet) 2-300
Number of Racks 3
Average Power Density per Rack (kW) 2
Total Power Load (kW) 6
Total Heat Load (kW) 7
Single, Double, Combo Corded Equipment Combo
Tier Level 2
Power Redundancy Methodology n/a
Power Availability (9's) 99.99
Incoming Power (phase) 3
Power Incoming // Outgoing (V) 208 // 208 / 120
Space Definition* No Raised Floor
False Ceiling or Ducting
Monitoring Requirement / User Remote / IT


Bill Of Materials

Foundation Racks 3
UPS Type 1 x NX
UPS Output (kVA each) 10
UPS Ancillaries -
UPS Standard Battery Runtime (minutes) 9
Static Transfer Switch -
Power Distribution SlimLine Distribution Cabinet
Managed Power Strips - MP 3
Cooling Type 1 x Challenger
Cooling Output (kW each / kW total) 9.8
Monitoring 1 x MP-S Access Server, 1 x OC web card and 1 x OC NIC card, 1 x Nform Software, 3 x Temperature Sensors, 1 x Multilink Shutdown Software
Service Recommendation Startup, Preventative Maintenance, Parts, Battery Services, Emergency Response, Remote Monitoring


Line Drawings


Power One-Line Drawing


Cooling One-Line Drawing

Monitoring One-Line Drawing