Assuring the Availability of Network Closets and Computer Rooms

Overview


Room size (square feet) 2-300
Number of Racks 3
Average Power Density per Rack (kW) 4
Total Power Load (kW) 12
Total Heat Load (kW) 13
Single, Double, Combo Corded Equipment Single
Tier Level 3
Power Redundancy Methodology N+1
Power Availability (9's) 99.999
Incoming Power (phase) 1
Power Incoming // Outgoing (V) 208 // 208 / 120
Space Definition* No Raised Floor
False Ceiling or Ducting
Monitoring Requirement / User Local / IT


Bill Of Materials

Foundation Racks 3
UPS Type 1 x Nfinity
UPS Output (kVA each) 20
UPS Ancillaries -
UPS Standard Battery Runtime (minutes) 7
Static Transfer Switch -
Power Distribution maintenance bypass panel with distribution
Managed Power Strips - MP 3
Cooling Type 2 x Mini-Mate (1 on/1 standby)
Cooling Output (kW each / kW total) 14/28
Monitoring 1 x MP-S Access Server, 1 x OC web card and 2 x OC NIC cards, 1 x Nform Software, 3 x Temperature Sensors, 1 x Multilink Shutdown Software
Service Recommendation Startup, Preventative Maintenance, Parts, Battery Services, Emergency Response, Remote Monitoring


Line Drawings


Power One-Line Drawing


Cooling One-Line Drawing

Monitoring One-Line Drawing