      Scenario 17



Related PDF's Corporate Capabilities Brochure

Assuring the Availability of Network Closets and Computer Rooms

Overview


Room size (square feet) 2,500
Number of Racks 36
Average Power Density per Rack (kW) 10
Total Power Load (kW) 360
Total Heat Load (kW) 383
Single, Double, Combo Corded Equipment Combo
Tier Level 4
Power Redundancy Methodology dual bus
Power Availability (9's) 99.9999999
Incoming Power (phase) 3
Power Incoming // Outgoing (V) 480 // 480
Space Definition* Raised Floor
Monitoring Requirement / User Remote / IT and Facilities


Bill Of Materials

Foundation Racks 36 (9 per row - hot aisle/cold aisle)
UPS Type 2 x 610 (w/ battery cabinets)
UPS Output (kVA each) 500 each
UPS Ancillaries LBS Controller (wall mount)
UPS Standard Battery Runtime (minutes) -
Static Transfer Switch STS/PDU
Power Distribution 2 x FPC
Managed Power Strips - MP 72
Cooling Type 2 x DS (Dual Compressors) 36 x XDV, 2 x XDC (Dual Pumps + Compressors
Cooling Output (kW each / kW total) 80/160 + 320
Monitoring 2 x MP-S Access Servers, 4 x OC web cards, 1 x Nform Software, 1 x Liqui-tech Panel with cable, 1 x Multilink Shutdown Software, 2 x BDS40 Battery
Service Recommendation Startup, Preventative Maintenance, Parts, Battery Services, Emergency Response, Remote Monitoring, Technical & Testing Service
Automatic Transfer Switch ATS


Line Drawings


Power One-Line Drawing

Cooling One-Line Drawing

Monitoring One-Line Drawing