Overview
| Room size (square feet) |
625 |
| Number of Racks |
12 |
| Average Power Density per Rack (kW) |
8 |
| Total Power Load (kW) |
96 |
| Total Heat Load (kW) |
105 |
| Single, Double, Combo Corded Equipment |
Combo |
| Tier Level |
4 |
| Power Redundancy Methodology |
dual bus |
| Power Availability (9's) |
99.99999 |
| Incoming Power (phase) |
3 |
| Power Incoming // Outgoing (V) |
480 // 208 / 120 |
| Space Definition* |
Raised Floor |
| Monitoring Requirement / User |
Remote / IT and Facilities |
Bill Of Materials
| Foundation Racks |
12 (6 per row - hot aisle/cold aisle) |
| UPS Type |
2 x Npower (w/ battery cabinets) |
| UPS Output (kVA each) |
130 each |
| UPS Ancillaries |
LBS Controller (wall mount) |
| UPS Standard Battery Runtime (minutes) |
5 |
| Static Transfer Switch |
STS2 w/ Distribution |
| Power Distribution |
2 x SlimLine Distribution Cabinets, 2 x FDC |
| Managed Power Strips - MP |
24 |
| Cooling Type |
4 x DS (2 on/2 standby) |
| Cooling Output (kW each / kW total) |
59/236 |
| Monitoring |
2 x MP-S Access Servers, 6 x OC web cards, 1 x Nform Software, 1 x Liquitech
Panel with cable, 1 x Multilink Shutdown Software |
| Service Recommendation |
Startup, Preventative Maintenance, Parts, Battery Services, Emergency
Response, Remote Monitoring, Technical & Testing Service |
| Automatic Transfer Switch |
ATS |
Line Drawings
Power
One-Line Drawing
|
Cooling
One-Line Drawing
|
Monitoring
One-Line Drawing
|
|
|
|