      Scenario 13



Related PDF's

Corporate Capabilities Brochure

Assuring the Availability of Network Closets and Computer Rooms

Overview


Room size (square feet) 625
Number of Racks 10
Average Power Density per Rack (kW) 5
Total Power Load (kW) 50
Total Heat Load (kW) 55
Single, Double, Combo Corded Equipment Single
Tier Level 3
Power Redundancy Methodology 1+1
Power Availability (9's) 99.9999
Incoming Power (phase) 3
Power Incoming // Outgoing (V) 208 // 208 / 120
Space Definition* No Raised Floor
Monitoring Requirement / User Remote / IT and Facilities


Bill Of Materials

Foundation Racks 10 (5 per row - hot aisle/cold aisle)
UPS Type 2 x Npower (w/ battery cabinets)
UPS Output (kVA each) 60 each
UPS Ancillaries paralleling cabinet
UPS Standard Battery Runtime (minutes) 5
Static Transfer Switch -
Power Distribution 1 x FDC
Managed Power Strips - MP 10
Cooling Type 2 x DS (1 on/1 standby)
Cooling Output (kW each / kW total) 59/118
Monitoring 1 x MP-S Access Servers, 4 x OC web cards, 1 x Nform Software, 1 x Liquitech Panel with cable, 1 x Multilink Shutdown Software
Service Recommendation Startup, Preventative Maintenance, Parts, Battery Services, Emergency Response, Remote Monitoring, Technical & Testing Service


Line Drawings


Power One-Line Drawing

Cooling One-Line Drawing

Monitoring One-Line Drawing