Assuring the Availability of Network Closets and Computer Rooms

Overview


Room size (square feet) 440
Number of Racks 10
Average Power Density per Rack (kW) 5
Total Power Load (kW) 50
Total Heat Load (kW) 55
Single, Double, Combo Corded Equipment Single
Tier Level 2
Power Redundancy Methodology n/a
Power Availability (9's) 99.99
Incoming Power (phase) 3
Power Incoming // Outgoing (V) 208 // 208 / 120
Space Definition* No Raised Floor
Monitoring Requirement / User Remote / IT and Facilities


Bill Of Materials

Foundation Racks 10 (5 per row - hot aisle/cold aisle)
UPS Type 1 x Npower (w/ battery cabinet)
UPS Output (kVA each) 60
UPS Ancillaries -
UPS Standard Battery Runtime (minutes) 5
Static Transfer Switch -
Power Distribution 1 x FDC
Managed Power Strips - MP 10
Cooling Type 1 x DS
Cooling Output (kW each / kW total) 59
Monitoring 1 x MP-S Access Servers, 2 x OC web cards, 4 x Nform Software, 1 x Multilink Shutdown Software
Service Recommendation Startup, Preventative Maintenance, Parts, Battery Services, Emergency Response, Remote Monitoring