Assuring the Availability of Network Closets and Computer Rooms
Overview
| Room size (square feet) |
440 |
| Number of Racks |
10 |
| Average Power Density per Rack (kW) |
5 |
| Total Power Load (kW) |
50 |
| Total Heat Load (kW) |
55 |
| Single, Double, Combo Corded Equipment |
Single |
| Tier Level |
2 |
| Power Redundancy Methodology |
n/a |
| Power Availability (9's) |
99.99 |
| Incoming Power (phase) |
3 |
| Power Incoming // Outgoing (V) |
208 // 208 / 120 |
| Space Definition* |
No Raised Floor |
| Monitoring Requirement / User |
Remote / IT and Facilities |
Bill Of Materials
| Foundation Racks |
10 (5 per row - hot aisle/cold aisle) |
| UPS Type |
1 x Npower (w/ battery cabinet) |
| UPS Output (kVA each) |
60 |
| UPS Ancillaries |
- |
| UPS Standard Battery Runtime (minutes) |
5 |
| Static Transfer Switch |
- |
| Power Distribution |
1 x FDC |
| Managed Power Strips - MP |
10 |
| Cooling Type |
1 x DS |
| Cooling Output (kW each / kW total) |
59 |
| Monitoring |
1 x MP-S Access Servers, 2 x OC web cards, 4 x Nform Software, 1 x Multilink
Shutdown Software |
| Service Recommendation |
Startup, Preventative Maintenance, Parts, Battery Services, Emergency
Response, Remote Monitoring |
Line Drawings
Power
One-Line Drawing
|
Cooling
One-Line Drawing
|
Monitoring
One-Line Drawing
|
|
|
|