|
|
Related PDF's
Corporate Capabilities Brochure
Assuring the Availability of Network Closets and Computer Rooms
Overview
| Room size (square feet) |
2-300 |
| Number of Racks |
3 |
| Average Power Density per Rack (kW) |
5 |
| Total Power Load (kW) |
15 |
| Total Heat Load (kW) |
16 |
| Single, Double, Combo Corded Equipment |
Single |
| Tier Level |
3 |
| Power Redundancy Methodology |
1+1 |
| Power Availability (9's) |
99.999 |
| Incoming Power (phase) |
3 |
| Power Incoming // Outgoing (V) |
208 // 208 / 120 |
| Space Definition* |
No Raised Floor
False Ceiling or Ducting |
| Monitoring Requirement / User |
Local / IT |
Bill Of Materials
| Foundation Racks |
3 |
| UPS Type |
2 x NX |
| UPS Output (kVA each) |
20 each |
| UPS Ancillaries |
paralleling cabinet |
| UPS Standard Battery Runtime (minutes) |
9 |
| Static Transfer Switch |
- |
| Power Distribution |
SlimLine Distribution Cabinet |
| Managed Power Strips - MP |
3 |
| Cooling Type |
2 x Challenger (1 on, 1 standby) |
| Cooling Output (kW each / kW total) |
16/32 |
| Monitoring |
1 x MP-S Access Server, 2 x OC web cards and 2 x OC NIC cards, 1 x Nform
Software, 3 x Temperature Sensors, 1 x Multilink Shutdown Software |
| Service Recommendation |
Startup, Preventative Maintenance, Parts, Battery Services, Emergency
Response, Remote Monitoring |
Line Drawings
Power
One-Line Drawing br> |
Cooling
One-Line Drawing
|
Monitoring
One-Line Drawing
|
|
|
|