Family NameLiebert Datamate™
Model NumberDM 1.5 Tons (5.3kW)DM 2, 3 Tons (7, 10.5kW)
Input AC Specifications
Voltage - Phase - Frequency208/230 - 1 - 50, 208/230 - 1 - 60208/230 - 1 - 50, 208/230 - 1 - 60
General Specifications
Cooling TypesAir, water, glycol, chilled waterAir, water, glycol, chilled water
Nominal Capacity, Tons (kw)1.5 (5.3)2, 3 (7, 10.5)
Mounting LocationFloor, WallFloor, Wall
Compressor
Qty11
LocationUnit or Heat RejectionUnit or Heat Rejection
TypeReciprocating & ScrollScroll
# of cooling circuits11
Refrigerant TypeR22R22
Physical Data
Unit Height, inches (mm)32 (813)32 (813)
Unit Width, inches (mm)46.5 (1181)64.1 (1628)
Unit Depth, inches (mm)11.9 (302)11.9 (302)
Unit Footprint, ft2 (m2)3.8 (0.4)5.3 (0.5)
Unit Weight, lbs. (kg)230 (104)365 (165)
Unit Footprint w/ Service clearances, ft2 (m2)14.8 (1.4)20.4 (1.9)
Feature Set
Blower TypeCentrifugalCentrifugal
Air Distribution TypeTop GrilleTop Grille
Humidifier TypeSteam CanisterSteam Canister
Reheat TypesElectricElectric
Control TypeWall Display/MicroprocessorWall Display/Microprocessor
Service AccessFront onlyFront only
Heat RejectionAir-Cooled: Split Indoor or Outdoor Condensing unit; Water/Glycol: Integral or Split Indoor Chilled Water, Air-Cooled: Split Indoor or Outdoor Condensing unit; Water/Glycol: Integral or Split Indoor
Agency/Certification/Conformance
Agency ApprovalCSACSA
Warranty
Labor Standard90 days after start-up; 1 year optional90 days after start-up; 1 year optional
Parts Standard1 Year1 Year
Compressor Standard1 Year1 Year