Family NameLiebert FPC™  
Model NumberFPC 15-125 KVAFPC 150-225 KVAFPC 300 KVA
Power Rating  
Rating, kVA15,30,50,75,100, 125150, 200, 225300
Rating, kW15,30,50,75,100, 125150, 200, 225300
Input AC Specifications 
Phase333
Power Factor0.75 to 1.0%0.75 to 1.00.75 to 1.0
Input Current, Amps19 to 155185 to 278372
Input Frequency, Hz606060
Frequency Range, Hz+/-0.5Hz+/-0.5Hz+/-0.5Hz
Surge ProtectionANSI/IEEE C62.41 Category B3ANSI/IEEE C62.41 Category B3ANSI/IEEE C62.41 Category B3
Input Circuit Breaker, Amps25 to 200250 to 350500
Input Voltage480480480
Input Connections or Input Cord/Plug TypeJunction Box w/10 ft field wired cableJunction Box w/10 ft field wired cableJunction Box w/10 ft field wired cable
Transformer Specifications 
TypeDouble ShieldedDouble ShieldedDouble Shielded
WindingsCopperCopperCopper
NEMA StandardType 1Type 1Type 1
Temperature Rise150°C150°C150°C
Impedance3.8% to 5.3%4.5% to 4.7%3.7%
Taps6 (-10% to +5%)6 (-10% to +5%)6 (-10% to +5%)
Overload Protection2 Sensors per winding (180°C & 200°C) 2 Sensors per winding (180°C & 200°C) 2 Sensors per winding (180°C & 200°C)
Output AC Specifications 
Nominal Voltage208/120208/120208/120
Output Waveform SinewaveSinewaveSinewave
Efficiency96.5 to 98%96.5 to 98%96.5 to 98%
Distortion0.5% Max Additive0.5% Max Additive0.5% Max Additive
Crest FactorUp to 3.5Up to 3.5Up to 3.5
Branch Circuit Breakers84168168
Panelboards or Receptacles2 Panelboards4 Panelboards4 Panelboards
User Interface 
LED's IndicatorsNoNoNo
Display TypeLCDLCDLCD
Communications  
Communications StandardRS-422, RS-232RS-422, RS-232RS-422, RS-232
Communications OptionsNIC, LDMNIC, LDMNIC, LDM
Physical Data 
ColorBlackBlackBlack
Unit Height, inches (mm)78.5 (1994)78.5 (1994)78.5 (1994)
Unit Width, inches (mm)23.5 (597)47 (1194)47 (1194)
Unit Depth, inches (mm)39.5 (1003)39.5 (1003)39.5 (1003)
Unit Weight, lbs. (kg)1010 (458) to 1650 (748)2490 (1129) to 2800 (1270)2845 (1290)
Shipping Height, inches (mm)84 (2134)84 (2134)84 (2134)
Shipping Width, inches (mm)48 (1220)54 (1372)54 (1372)
Shipping Depth, inches (mm)48 (1220)70 (1778)70 (1778)
Shipping Weight, lbs. (kg)1100 (499) to 1740 (789)2630 (1193) to 2940 (1334)2940 (1334)
Environmental 
Operating Temperature, Minimum °F (°C)32 (0)32 (0)32 (0)
Operating Temperature, Maximum °F (°C)104 (40)104 (40)104 (40)
Storage Temperature, Minimum °F (°C)-67 (-55)-67 (-55)-67 (-55)
Storage Temperature, Maximum °F (°C)185 (85)185 (85)185 (85)
Relative Humidity0% to 95%, Non Condensing0% to 95%, Non Condensing0% to 95%, Non Condensing
Operating Elevation, ft. (m)Up to 6,600 (2,000) Up to 6,600 (2,000) Up to 6,600 (2,000)
Storage Elevation, ft. (m)to 40,000 (12,200 )to 40,000 (12,200 )to 40,000 (12,200 )
Sound Emission/Audible NoiseANSI C89 ANSI C89 ANSI C89
Heat Dissipation0.73KW to 3.37KW3.66KW to 4.63KW5.40KW
CoolingConvection Convection Redundant Fans
Options 
Optional ItemsInput Lightning/Surge Arrester, Output Surge Suppression Module, Subfeed Output Circuit Breaker, K-Rated Transformer, Floor Pedestals, Network Interface Card (NIC), Liebert Distribution Monitoring (LDM)Input Lightning/Surge Arrester, Output Surge Suppression Module, Subfeed Output Circuit Breaker, K-Rated Transformer, Floor Pedestals, Network Interface Card (NIC), Liebert Distribution Monitoring (LDM)Input Lightning/Surge Arrester, Output Surge Suppression Module, Subfeed Output Circuit Breaker, K-Rated Transformer, Floor Pedestals, Network Interface Card (NIC), Liebert Distribution Monitoring (LDM)
Agency/Certification/Conformance 
SafetyUL 60950, ANSI, CSA, NEC, NEMA, NFPA 75UL 60950, ANSI, CSA, NEC, NEMA, NFPA 75UL 60950, ANSI, CSA, NEC, NEMA, NFPA 75
TransportationISTA - Procedure 1HISTA - Procedure 1HISTA - Procedure 1H
RFI/EMIFCC Part 15 EMI Class AFCC Part 15 EMI Class AFCC Part 15 EMI Class A
Warranty 
Standard1 year or 18 months after ship date1 year or 18 months after ship date1 year or 18 months after ship date